Duravent Retail – Venting Industry Leader

MODEL BV

Type B Gas Vent Systems

Our non-positional lock system on the DuraVent® BV Gas Vent is the best lock system on the market today. The incorporation of the DuraTab® feature simply improves our lock system by adding flexibility and meeting market needs.

The BV line of DuraVent round vent pipe and fittings is designed for use on approved gas appliances in residential and light commercial and industrial applications.

DuraLock® Locking System

GroupImage_BV
ITEM CLEARANCE - SEE NOTE 1 MAX HEIGHT OUTER TUBE Ø MATERIALS LOCKING DEVICE UL LISTING
Type B Vent Round 3″-8″ (USA)
1 inch
100 feet
1/2″ larger than ID
Inner – .012″ Aluminum Outer – .018″ Galvanized
DuraLock & DuraTab
MH2848
Type B Vent Round 3″-8″ (CAN)
1 inch
100 feet
1/2″ larger than ID
Inner – .012″ Aluminum Outer – .018″ Galvalume*
DuraLock & DuraTab
MH2848
Round 10″ to 18″ – See note 2
1 inch
100 feet
1″ larger than ID
Inner – .014″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
Round 20″ to 30″ (USA) See note 2
1 inch
100 feet
1″ larger than ID
Inner – .023″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
Round 20″ to 24″ (CAN) See note 2
1 inch
100 feet
1″ larger than ID
Inner – .023″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
Round 26″ to 30″ (CAN) See note 2
2 inch
100 feet
1″ larger than ID
Inner – .023″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
Oval Type B Gas Vent 4″ and 5″
1 inch – See Note 5
See Note 3
4″: 2 1/2″ x 7 1/4″ or 5″: 3 1/8″ x 10 7/8″
Inner – .012″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
Oval Type B Gas Vent 6″
1 inch – See Note 5
See Note 3
3 1/4″ x 12″
Inner – .012″ Aluminum Outer – .018″ Galvanized
DuraLock
MH2848
DuraConnect I Flex 3″ and 4″
1 inch
See Note 4
NA
.012″ Aluminum Flexible, .018″ Galvalume Fittings
DuraLock & DuraTab
MH17667
DuraConnect II Flex 3″ to 5″
1 inch
See Note 4
1/4″ larger than ID
.006″ 2 Ply Aluminum Flex, .018″ Galvalume Fittings
DuraLock & DuraTab
MH17667

*In Canada, the outer tube material is galvalume for 3″ to 8″ pipe length. All other 3″ to 8″ fittings have a galvanized outer tube.

Notes: Gas Vent Specification Chart

  1. Clearance to combustibles is the air space between vent and combustibles.
  2. For maximum height refer to the appliance manufacturer installation instructions and the National Fuel Gas Code NFPA 54 or the Canadian Fuel Gas Installation Code CSA-149.1-00. For taller applications refer to DuraVent Sizing Handbook.
  3. When oval is used on wall furnaces, minimum height required from bottom of furnace to cap is 12′, minimum 16″ stud space.
  4. Limited by sizing tables.
  5. BVO 4″ & 5″ oval can be installed in a 2″ x 4″or a 2″ x 6″ stud wall. BVO 6″ oval can be installed in a 2″ x 6″ stud wall.
Let Us Help!